Model TR-Jr.
Fully Automatic Single Phase Ratiometer

Download TR-Jr. PDF
Specifications

Model:
TR Jr.
Size: L: 14" (356 mm) W: 10" (254 mm) H: 6" (155 mm).
Weight: 10 lbs. (4.5 kg).
Input Power: 100 to 240 Vac 50 / 60 Hz Autoranging.
Output Voltage: User Selectable: 10 & 40 Vac
Panel Display: LCD Graphic with back lighting.
Front Panel: Sealed, Piezo-electric actuation.
Interface: 9 Pin RS232 Serial / 25 Pin Centronics Parallel.
Memory Storage: Internally stores complete test results with 33 tap measurements each.

Measurement Parameters

Turns Ratio Range:
0.8 ... 4000 Resolution: 5 Digits

Accuracy

Range
0.8 ... 2000 ± 0.1 % with 40 Volt ± 0.15 % with 10 Volt
Range 2001 ... 4000 ± 0.2 % with 40 Volt ± 0.4 % with 10 Volt
Current
Range: 0 ... 1 Ampere
Accuracy: ± 0.001 Ampere
Resolution: 0.0001 Ampere

Temperature:
Operating - 10° C to 60° C Storage - 40° C to 70° C

Cable Set / Accessories:
Cable Set Includes: H & X leads (single phase, dual color, 12’ lengths), Power Cord (8’), Operation manual, Test Certificate.

TR-Jr Features: Standard Items

Laboratory accuracy of measurements of Turns Ratio and Current
System is housed in a rugged, lightweight, water-proof case.
Graphical display of tap changer test results.
Fully automatic, continuous operation bridge.
Internal storage for test results.
Single push button operation.
Two voltage ranges 10V, 40V.
Comparison with a nominal ratio.
Load on test object < 0.05 VA.
Heavy duty protection circuitry.
Centronics (Parallel) & RS232 (Serial) Interface.
Safety Emergency shut off.
Self calibrating.
Five year standard warranty
Jr Features: Optional Items

Part No-
TJ 01 -30 ft Extension cable.
Part No- TJ 02 -Custom clamping devices (user specified).
Part No- TJ 03 -Battery Operation.
Part No- TJ 04 -Windows based control & operation.
SPECIFICATIONS ARE SUBJECT TO CHANGE AT ANY TIME
Back to Products Page